Internal Winding Fault Protection for Shunt Reactors
2011
Aleksandrs Dolgicers, Dmitrijs Antonovs

Existing protection techniques for shunt reactors can’t guarantee sufficient sensitivity for inter-winding faults due to limited precision of current transformer. To solve this usage problem of input resistance of resonance contour formed by reactor bank inductance attaching wiring capacitance is proposed. Difference between input resistance profiles of damaged and healthy bank is used as a fault criterion.


Keywords
shunt reactors protection, impedance profile.

Dolgicers, A., Antonovs, D. Internal Winding Fault Protection for Shunt Reactors. Power and Electrical Engineering. Vol.28, 2011, pp.43-47. ISSN 1407-7345.

Publication language
English (en)
The Scientific Library of the Riga Technical University.
E-mail: uzzinas@rtu.lv; Phone: +371 28399196