Isolation Stage for Power Electronic Transformer: Dual Active Bridge vs Bi-Directional Current Doubler Rectifier
International Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM 2012): Proceedings 2012
viktor Beldjajev, Indrek Roasto, Jānis Zaķis

This paper compares two DC/DC converter topologies which are suitable for isolation stage of power electronic transformer. Paper provides loss analysis of dual active bridge and current doubler rectifier topologies in forward and reverse operating modes. In particular, the conduction and switching losses, as well as overall efficiency are estimated. In addition, the calculated losses and overall efficiency of both converters are verified with simulations and with experimental results on 1 kW experimental prototype.


Atslēgas vārdi
dual active bridge converter, bi-directional current doubler, power electronic transformer, solid state transformer, soft switching
DOI
10.1109/SPEEDAM.2012.6264545
Hipersaite
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=6264545

Beldjajev, v., Roasto, I., Zaķis, J. Isolation Stage for Power Electronic Transformer: Dual Active Bridge vs Bi-Directional Current Doubler Rectifier. No: International Symposium on Power Electronics, Electrical Drives, Automation and Motion (SPEEDAM 2012): Proceedings, Itālija, Sorrento, 20.-22. jūnijs, 2012. Piscataway: IEEE, 2012, 849.-854.lpp. ISBN 978-1-4673-1299-8. Pieejams: doi:10.1109/SPEEDAM.2012.6264545

Publikācijas valoda
English (en)
RTU Zinātniskā bibliotēka.
E-pasts: uzzinas@rtu.lv; Tālr: +371 28399196